Analysis of Reliability of 20 kV Distribution Network System in PT. PLN (Persero) ULP Panam With Reliability Index Assessment (RIA) Method

Analisis Keandalan Sistem Jaringan Distribusi 20 kV di PT. PLN (Persero) ULP Panam Menggunakan Metode Reliability Index Assessment (RIA)

Authors

  • Fanni Nurfadillah Fanni UIN Sultan Syarif Kasim

DOI:

https://doi.org/10.57152/ijeere.v2i2.468

Keywords:

reliability, distribution system, disturbance, blackout, SAIDI, SAIFI, CAIDI

Abstract

The disturbances that often occur in the distribution network of PT. PLN (Persero) ULP Panam greatly affects the reliability value of its distribution network, so it is necessary to evaluate the causes of disturbances and the reliability value of the ULP Panam distribution network using the Reliability Index Assessment (RIA) Method to determine whether the reliability of ULP Panam is still in good condition or not. In this study, using the Reliability Index Assessment (RIA) method and then comparing the calculation results with SPLN 68-2: 1986 and IEEE 1366-2003 with reliability indexes SAIDI, SAIFI and CAIDI. The results of the RIA calculation method obtained SAIDI values ??= 5.25 hours/plg/year, SAIFI = 9.32 times/plg/year, and CAIDI = 0.56 hours/plg/year. Based on SPLN 68-2:1986 SAIDI and CAIDI at PT. PLN ULP Panam can be said to be reliable because its value does not exceed the standard, namely SAIDI of 21 hours/year and CAIDI of 6.56 hours/plg/year. While the SAIFI index at PT. PLN ULP Panam is said to be unreliable because it exceeds the standard limit of SPLN 68-2:1986 which is 3.2 times/year. However, if based on the IEEE 1366-2003 (International) standard, the SAIDI and SAIFI indexes of PT. PLN ULP Panam is said to be unreliable because it exceeds the standard limit, namely SAIDI 2.3 hours/year and SAIFI 1.45 times/year, while the CAIDI reliability index of PT. PLN ULP Panam is said to be reliable because its value does not exceed the IEEE 1366-2003 standard limit of 1.47 hours/year

References

M. Imran, A. Bintoro, and Ezwarsyah, “Analisa Keandalan Sistem Distribusi Tenaga Listrik Untuk Wilayah Kota Lhokseumawe Di PT. PLN (Persero) Rayon Kota Lhokseumawe,” J. Energi Elektr., vol. 08, no. 1, pp. 42–47, 2019.

D. O. E. K. Putra, H. R. . M. Gozali, and S. Prasetyono, “Analisis Perbandingan Keandalan Sistem Jaringan Distribusi Berkonfigurasi Radial dan Loop Menggunakan Metode Ria (Reliability Index Assessment),” J. Arus Elektro Indones. , pp. 63–67, 2020.

R. A. Duyo, “Analisis Penyebab Gangguan Jaringan PadaDistribusi Listrik Menggunakan Metode Fault Tree Aalysis DI PT . PLN ( PERSERO ) Rayon Daya Makasssar,” J. Vertex Elektro, vol. 12, no. 02, p. 4, 2020.

M. E. Ir. Slamet Suripto, “Sistem Tenaga Listrik,” ELTEK, Vol 11 Nomor 01, pp. 1–293, 2017.

M. G. C. Purba Wisesa, S. Bachri M, “Analisis keandalan sistem distribusi 20 kv di pt. pln (persero) apj banyuwangi dengan metode reliability network equivalent approach ( 20,” pp. 1–6, 2015.

“PROFIL PERUSAHAAN,” 2022. https://web.pln.co.id/tentang-kami/profil-perusahaan

B. A. B. Ii, “Mohamad Tresna Wikarsa, FT UI, 2010.,” Skripsi, vol. 14, no. 1, pp. 3–26, 2010.

T. D. A. N. Distribusi and R. Syahputra, “Transmisi Dan Distribusi Tenaga Listrik,” Long Range Plann., vol. 28, no. 4, p. 131, 1995.

D. Suswanto, “Analisis Gangguan Pada Jaringan Distribusi,” Sist. Distrib. Tenaga List., vol. 1, pp. 245–272, 2010.

N. I. Arifani and H. Winarno, “Analisis Nilai Indeks Keandalan Sistem Jaringan Distribusi Udara 20 Kv Pada Penyulang Pandean Lamper 1,5,8,9,10 Di Gi Pandean Lamper,” Gema Teknol., vol. 17, no. 3, pp. 131–134, 2015, doi: 10.14710/gt.v17i3.8929.

F. Yaser and A. A. Zakri, “Analisis tingkat keandalan jaringan distribusi 13,8 kv dengan menggunakan metode ria,” Jom Fteknik, vol. 6, no. 2, pp. 1–9, 2019.

H. Prabowo, Hernanda, I. G. N. Satriyadi, and O. Penangsang, “Studi Analisis Keandalan Sistem Distribusi Pabrik Semen Tuban Menggunakan Metode Reliability Index Assessment (RIA) dan Program Analisis Kelistrikan,” J. Tek. ITS, vol. 1, no. 1, pp. 87–90, 2012.

A. Soeprijanto and F. Penangsang, Ontoseno, “Studi Perbaikan Keandalan Jaringan Distribusi Primer Dengan Pemasangan Gardu Induk Sisipan Di Kabupaten Enrekang Sulawesi Selatan,” J. Tek. Its, vol. 1, no. 1, p. B-119-B-124, 2012.

T. Menda, “Sistem Pola Operasi Single Line Diagram Penyulang 20 Kv Pln Unit Layanan Pelanggan Panam,” p. 60.

Published

2022-12-24

How to Cite

[1]
F. N. Fanni, “Analysis of Reliability of 20 kV Distribution Network System in PT. PLN (Persero) ULP Panam With Reliability Index Assessment (RIA) Method: Analisis Keandalan Sistem Jaringan Distribusi 20 kV di PT. PLN (Persero) ULP Panam Menggunakan Metode Reliability Index Assessment (RIA)”, IJEERE, vol. 2, no. 2, pp. 104-112, Dec. 2022.